Manager View
Manager Dashboard
Overview of team performance, tasks & fleet health
0%
Completion Rate
0/13 tasks
0
Overdue Tasks
Require attention
87
Avg Health Score
0 critical assets
2/4
Available Techs
1 active work orders
Task Types
Task Status Overview
Cost Summary (Last 30 days)
Estimated Costs
$67,300
Actual Costs
$0
Variance
-$67,300
Team Performance
BESS High-Voltage Field Crew A
0%
completion
Liam Kerr (BESS Thermal & HV Specialist)
0%
completion
Elena Vance (HV BESS Lead)
0%
completion
Marcus Sterling (BMS & Cell Diagnostics)
0%
completion
Active Alerts (4)
DPSF 330kV TX-01 Dissolved Gas Analysis (DGA) Ethylene Spike
Online DGA monitor detected ethylene (C2H4) rising from 42 ppm to 98 ppm over 14 days during peak afternoon solar export (268 MWac).
Riverina BESS 2 Coolant Loop C3 ΔT Cell Spread Exceedance
Megapack Bank C3 cell temperature delta reached 6.8°C during FCAS Raise 6-second market dispatch event. Glycol flow rate 18% below nominal.
Darlington Point INV-Block-14 IGBT Phase B Thermal Derating
SMA Sunny Central 4600 UP Inverter Block 14 derated output by 22% at 39°C ambient due to IGBT heatsink thermal resistance degradation.
Whitsunday Solar Farm Row 42-58 NEXTracker Slew Gear Current High
Motor drive current on 16 tracker rows in Whitsunday Sector exceeded 4.8A during morning stow recovery.